BENTEC BHARTIA ENGINEERS PVT. LTD. |
GUARANTEED TECHNICAL PERTUCULARS |
PRODUCT : – RCCB (RESIDUAL CURRENT CIRCUIT BREAKAR) |
Sr. no. |
TECHNICAL SPECIFICATION |
1 |
Specifications |
IS : 12640-1 (2008) |
2 |
Number of modules |
2 for 2 Pole, 4 for 4 Pole |
3 |
Configuration |
2 Pole & 4 Pole |
4 |
Rated currents (In) |
2 Pole (16, 25, 40, 63) 4 Pole (16, 25, 40, 63) |
5 |
Sensitivity (IΔn) |
30mA, 100mA, 300mA |
6 |
Design & rated voltages (Un) |
2 Pole – 240V 4 Pole 240/415VAC |
7 |
Maximum operating voltage |
440V AC |
8 |
Test circuit voltage (up) |
240V AC |
9 |
Rated frequencies |
50Hz…..60 Hz |
10 |
Short circuit breaking capacity (Ics) |
10 kA with proper backup fuses |
11 |
Back – up fuse |
80 Amp gL – gG |
12 |
Climatic resistance |
As per IS : 12640-1 (2000) |
13 |
Shock resistance |
20g |
14 |
Vibration resistance |
>5g (f<=80Hz, duration >=30min) |
15 |
Line & load reversibility |
Available |
16 |
Electrical endurance |
2000 switching cycles (As per IS : 12640-1 (2000) |
17 |
Trip free mechanism |
Available |
18 |
ISI Marking |
Yes, License No. 5241855 |
19 |
Protection class |
IP 20 |
20 |
Temperature range |
T max = 55°C T min = -25° C |
21 |
Terminal capacity |
1.0 – 25 mm sq. |
22 |
Mounting |
Din rail mounting |
23 |
Weight (incl. packing box) |
2 Pole -0.235 kg.: 4 Pole- 0.400kg. |
24 |
Break time |
<0.04sec. |